Aricontrol System Turbulator - installed in a Series 7400 solid rubber wall-mounted distributor enclosure
The Aircontrol System automatically regulates one ormore turbulators based on room temperature and humidity. Fan speed is controlled continuously, ensuring demand-driven air circulation and an optimized indoor climate.
Operation can be performed either locally via a touch control panel or through a dashboard within the local network. An optional app with remote access is also available.
When integrated into the customer‘s network infrastructure, the built-in web interface can be used to control and monitor the turbulator system. In addition, all current operating and measurement data are displayed in real time. Two temperature sensors measure the temperatures in the floor and ceiling
areas. These values enable optimal turbulator control and help maintain the best possible indoor climate.
The ceiling temperature sensor can be operated either by:
2 × AAA batteries (included in the scope of delivery), or a 24VDC power supply.
The distribution enclosure is manufactured from vulcanized butyl rubber. It is halogen-free, UV-resistant, and resistant to oils, various acids, and alkalis. It is also unaffected by welding sparks and flying sparks.
Additional mechanical protection is provided by an extended protective rim. Four wall-mounting points, isolated from the wiring compartment, ensure complete protective insulation. The fuse components are housed beneath a robust, hinged Makrolon cover, providing protection against water splashes.
Entry
1/cable gland M25 (clamping range 9-18mm) bottom
3/cable gland M20 (clamping range 7-14mm) bottom
2/cable gland M16 (clamping range 3,5-10mm) bottom
Equipment
1/Miniserver Compact
1/AO Extension
1/Touch Pure Flex Tree, anthracite (mounted on the front panel)
1/Mean Well HDR-30-24 power supply
1/Air Room Climate Sensor, anthracite
(supplied separately for monitoring the upper room climate)
Control system supplied fully wired and ready for connection.
|
|
| Technical Data |
|
| Control Unit: |
Loxone Miniserver Compact AO Extension |
| Control Supply Voltage: |
24VDC (Mean Well power supply, DIN rail mounted) |
| Mains connection Distribution: |
230VAC, 50/60 Hz (L1, N, PE) |
| Speed Control Signal to Turbulator: |
0–10VDC (AQ1–AQ4, one output per turbulator group) |
| Digital Direction Reversal Signal: |
potential-free relay contact Q1 |
| Window Contact (Reverse): |
potential-free relay contact Q2 |
| Emergency Stop Input: |
digital input I1 |
| Turbulator Fault Signal Input: |
digital input I2 |
| Operator Interface: |
Loxone Touch Pure Flex Tree (Tree-Bus) |
| Sensors: |
Air Room Climate Sensor (ceiling) integrated sensor in the touch panel (floor level) |
| Dimensions (W×H×D): |
266 x 370 x 133 (112) mm |